Address

Newton City Hall
1000 Commonwealth Ave
Newton Centre, MA 02459

617-796-1000
TDD/TTY 617-796-1089

Hours

Monday - Friday
8:30am-5:00pm

Tuesday
8:30am- 8:00pm

Contact the WebTeam

Downloadable Forms from the Newton Fire Department

Process for Review / Approval of Fire Protective Systems Installations

Applications for building permits

All applications for building permits have to be reviewed/ approved by the Newton Fire Department

Residential building permits

All reviews for residential building permit applications must be done by appointment. To schedule an appointment please call 617-796-2230. Please be aware that there is a $50 fee for this approval.

You need the following:

  • A description of the work to  be covered by the permit for which the application is made
  • 3 sets of floor plans detailing the locations of all required fire protection systems, including smoke and carbon monoxide detectors, fire sprinklers (if required).

Commercial building permits

All reviews for commercial building permits must be done by appointment. To schedule an appointment please call 617-796-2230.
 
Required documents to accompany an application for a building permit shall include the following:

  • Narrative report:

a. Basis (methodology) of design for the protection of the occupancy and hazards for compliance with 780 CMR and applicable NFPA standards, in the form of a narrative report.
b. Sequence of operation of all fire protection systems and operation in the form of a narrative report.
c. Testing criteria to be used for final system acceptance in the form of a narrative report.

2. Dedicated plans thatindicate the use of all rooms and document the location of all fire alarm equipment and devices in accordance with NFPA 72. The sequences of operation shall appear on the fire alarm plans as well as the narrative report.

3. Fire alarm equipment and device symbol legend.

4. Primary Power Connection.

5. Details of ceiling height and construction.

6. The interface of fire safety control functions

7. The location of any equipment or devices that directly interface with the fire alarm system.

8. Fire alarm system riser diagram.

 

Fire Protection Construction Documents

The following documents must be submitted prior to the installation of any protection equipment in order to be approved:

1. a. Basis (methodology) of design for the protection of the occupancy and hazards for compliance with 780 CMR and applicable NFPA Standards, in the form of a narrative report.
1.b. Sequence of operation of all fire protection systems and operation in the form of a narrative report.
1.c. Testing criteria to be used for final system acceptance in the form of a narrative report.
2. Building and site access for fire fighting and/or rescue vehicle(s) and personnel.
3. Fire hydrant(s) location and water supply information.
4. Type/description and design layout of the automatic sprinkler system(s).
5. Automatic sprinkler system(s) control equipment location.
6. Type/description and design layout of the automatic standpipe system(s).
7. Standpipe system hose valve(s) type and location.
8. Fire department siamese connection type(s) and location.
9. Type/description and design layout of the fire protective signaling system(s).
10. Fire protective signaling system(s) control equipment and remote annunciator
location.
11. Type/description and design layout of the smoke control or exhaust system(s).
12. Smoke control or exhaust system(s) control equipment location.
13. Building life safety system features (auxiliary functions) required to be
integrated as part of the fire protective signaling system(s).
14. Type/description and design layout of the fire extinguishing system(s).
15. Fire extinguishing system(s) control equipment location.
16. Fire protection system(s) equipment room location.
17. Fire protection system(s) equipment identification and operation signs.
18. Fire protection system(s) alarm/ supervisory signal transmission method and location.
19. Fire command center location.
20. Type/description and location of any emergency alarm system.
21. Type/description and location of any carbon monoxide protection.

Fire protection system  plans
All fire protection system plans shall contain sufficient information to identify the occupancy, hazards, system and equipment arrangements, system and equipment sizing, systems specifications, systems sequence(s) of operation and design/engineering calculations.

Construction documents required prior to the installation of fire alarm equipment or devices

Required documents shall include:

1. Manufacturers, models numbers and listing information for equipment, devices and materials.
2. Circuitry layout, conductor types and sizes.
3. Voltage drop calculations
4. Battery calculations

 

You will need Adobe Acrobat to view these forms.

Application for Fire Permit 

Request for Acceptance test

Owner's Authorization Form

Fire Alarm System Application

Master Box Application

 

 

Back to Fire HQ